본문으로 건너뛰기
cccskills
무료GitHub에 공개

detecting-modbus-command-injection-attacks

Monitor Modbus traffic in industrial control networks to identify unauthorized writes, unusual commands, and departures from normal communication. Use packet analysis and intrusion detection rules to investigate suspected controller changes and produce reports with recommended actions.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

원문원문 설명 보기

Detect command injection against Modbus TCP/RTU in ICS/SCADA environments by monitoring unauthorized writes, anomalous function codes, malformed frames, and deviations from communication baselines using ICS-aware IDS and deep packet inspection. Use when deploying IDS for Modbus OT networks, investigating unauthorized PLC register/coil changes, or responding to FrostyGoop-style Modbus attacks.

설치 방법 보기

이럴 때 유용합니다

  • Investigating unauthorized changes to PLC registers
  • Setting up Modbus intrusion detection rules
  • Checking communication patterns after a suspected compromise
  • Investigating FrostyGoop-style attacks

포함된 파일(4)

  • SKILL.md20.1 KB
  • LICENSE11.0 KB
  • references/api-reference.md1.6 KB
  • scripts/agent.py5.1 KB

SKILL.md(원문)

설치하기 전에 에이전트에게 전달되는 지시 내용을 확인할 수 있습니다.

Detecting Modbus Command Injection Attacks

When to Use

  • When deploying intrusion detection for environments using Modbus TCP (port 502) or Modbus RTU
  • When investigating suspected unauthorized modifications to PLC registers or coils
  • When building detection analytics for OT SOC monitoring Modbus-heavy environments
  • When responding to FrostyGoop-style attacks that leverage Modbus TCP for operational impact
  • When performing baseline validation after a suspected compromise of a Modbus master

Do not use for detecting attacks on non-Modbus protocols (see detecting-dnp3-protocol-anomalies for DNP3), for general IT network intrusion detection, or for Modbus device configuration (see performing-ot-vulnerability-scanning-safely).

Prerequisites

  • Network SPAN/TAP on the segment carrying Modbus TCP traffic (typically port 502)
  • Baseline of normal Modbus communication patterns (masters, slaves, function codes, register ranges, polling intervals)
  • Suricata, Zeek, or commercial OT IDS deployed with Modbus protocol parsers enabled
  • Understanding of Modbus function codes used in the environment (read vs write operations)
  • Access to PLC programming documentation to validate expected register ranges

Workflow

Step 1: Build Modbus Communication Baseline

Capture and analyze normal Modbus traffic to establish what constitutes legitimate communication patterns.

#!/usr/bin/env python3
"""Modbus Command Injection Detector.

Monitors Modbus TCP traffic for unauthorized write operations, anomalous
function codes, and deviations from established communication baselines.
Detects attacks like FrostyGoop that use Modbus TCP for operational impact.
"""

import json
import struct
import sys
import time
from collections import defaultdict
from datetime import datetime
from typing import Dict, List, Optional, Set, Tuple

try:
    from scapy.all import sniff, IP, TCP
except ImportError:
    print("Install scapy: pip install scapy")
    sys.exit(1)


# Modbus function code definitions
MODBUS_READ_FUNCTIONS = {1, 2, 3, 4}
MODBUS_WRITE_FUNCTIONS = {5, 6, 15, 16}
MODBUS_DIAGNOSTIC_FUNCTIONS = {8, 17, 43}

MODBUS_FUNC_NAMES = {
    1: "Read Coils", 2: "Read Discrete Inputs",
    3: "Read Holding Registers", 4: "Read Input Registers",
    5: "Write Single Coil", 6: "Write Single Register",
    8: "Diagnostics", 15: "Write Multiple Coils",
    16: "Write Multiple Registers", 17: "Report Slave ID",
    22: "Mask Write Register", 23: "Read/Write Multiple Registers",
    43: "Encapsulated Interface Transport",
}


class ModbusAlert:
    """Represents a detected Modbus anomaly."""

    def __init__(self, severity: str, alert_type: str, src_ip: str,
                 dst_ip: str, unit_id: int, func_code: int,
                 description: str, mitre_technique: str = ""):
        self.timestamp = datetime.now().isoformat()
        self.severity = severity
        self.alert_type = alert_type
        self.src_ip = src_ip
        self.dst_ip = dst_ip
        self.unit_id = unit_id
        self.func_code = func_code
        self.func_name = MODBUS_FUNC_NAMES.get(func_code, f"Unknown FC {func_code}")
        self.description = description
        self.mitre_technique = mitre_technique

    def __str__(self):
        return (
            f"[{self.severity}] {self.alert_type} | {self.src_ip} -> {self.dst_ip} "
            f"| Unit {self.unit_id} | {self.func_name} | {self.description}"
        )


class ModbusInjectionDetector:
    """Detects Modbus command injection attacks."""

    def __init__(self, baseline_file: Optional[str] = None):
        self.alerts: List[ModbusAlert] = []
        self.packet_count = 0
        self.modbus_count = 0

        # Baseline data
        self.authorized_masters: Set[str] = set()
        self.authorized_pairs: Set[Tuple[str, str]] = set()
        self.allowed_write_sources: Set[str] = set()
        self.allowed_function_codes: Dict[str, Set[int]] = defaultdict(set)
        self.allowed_register_ranges: Dict[str, List[Tuple[int, int]]] = defaultdict(list)
        self.polling_intervals: Dict[str, float] = {}
        self.last_seen: Dict[str, float] = {}

        # Counters for rate detection
        self.write_counts: Dict[str, List[float]] = defaultdict(list)

        if baseline_file:
            self.load_baseline(baseline_file)

    def load_baseline(self, filepath: str):
        """Load established Modbus communication baseline."""
        with open(filepath, "r") as f:
            baseline = json.load(f)

        for session_key, data in baseline.get("modbus_baselines", {}).items():
            src, dst = session_key.split("->")
            self.authorized_pairs.add((src.strip(), dst.strip()))
            self.authorized_masters.add(src.strip())

            fc_set = set(data.get("allowed_function_codes", []))
            self.allowed_function_codes[session_key] = fc_set

            if fc_set & MODBUS_WRITE_FUNCTIONS:
                self.allowed_write_sources.add(src.strip())

            for reg_range in data.get("register_ranges", []):
                self.allowed_register_ranges[session_key].append(
                    (reg_range["start"], reg_range["end"])
                )

            if data.get("polling_interval_avg_sec"):
                self.polling_intervals[session_key] = data["polling_interval_avg_sec"]

        print(f"[*] Baseline loaded: {len(self.authorized_pairs)} authorized pairs, "
              f"{len(self.allowed_write_sources)} authorized write sources")

    def parse_modbus_mbap(self, payload: bytes) -> Optional[dict]:
        """Parse Modbus TCP MBAP header and PDU."""
        if len(payload) < 8:
            return None

        transaction_id = struct.unpack(">H", payload[0:2])[0]
        protocol_id = struct.unpack(">H", payload[2:4])[0]
        length = struct.unpack(">H", payload[4:6])[0]
        unit_id = payload[6]
        func_code = payload[7]

        if protocol_id != 0:  # Not Modbus
            return None

        result = {
            "transaction_id": transaction_id,
            "protocol_id": protocol_id,
            "length": length,
            "unit_id": unit_id,
            "func_code": func_code,
        }

        # Parse register address and count for read/write operations
        if len(payload) >= 12 and func_code in (1, 2, 3, 4, 5, 6, 15, 16):
            result["start_address"] = struct.unpack(">H", payload[8:10])[0]
            result["quantity"] = struct.unpack(">H", payload[10:12])[0]

        return result

    def analyze_packet(self, pkt):
        """Analyze a network packet for Modbus command injection."""
        self.packet_count += 1

        if not pkt.haslayer(IP) or not pkt.haslayer(TCP):
            return

        tcp = pkt[TCP]
        if tcp.dport != 502 and tcp.sport != 502:
            return

        payload = bytes(tcp.payload)
        if not payload:
            return

        modbus = self.parse_modbus_mbap(payload)
        if not modbus:
            return

        self.modbus_count += 1
        src_ip = pkt[IP].src
        dst_ip = pkt[IP].dst
        session_key = f"{src_ip}->{dst_ip}"
        now = time.time()

        # Detection Rule 1: Unauthorized Modbus master
        if self.authorized_masters and src_ip not in self.authorized_masters:
            if tcp.dport == 502:
                self.alerts.append(ModbusAlert(
                    severity="CRITICAL",
                    alert_type="UNAUTHORIZED_MASTER",
                    src_ip=src_ip, dst_ip=dst_ip,
                    unit_id=modbus["unit_id"],
                    func_code=modbus["func_code"],
                    description=f"Unauthorized device {src_ip} sending Modbus commands to {dst_ip}",
                    mitre_technique="T0843 - Program Download",
                ))

        # Detection Rule 2: Unauthorized write operation
        if modbus["func_code"] in MODBUS_WRITE_FUNCTIONS:
            if self.allowed_write_sources and src_ip not in self.allowed_write_sources:
                self.alerts.append(ModbusAlert(
                    severity="CRITICAL",
                    alert_type="UNAUTHORIZED_WRITE",
                    src_ip=src_ip, dst_ip=dst_ip,
                    unit_id=modbus["unit_id"],
                    func_code=modbus["func_code"],
                    description=f"Write command from non-authorized source {src_ip}",
                    mitre_technique="T0855 - Unauthorized Command Message",
                ))

            # Track write frequency for rate anomaly detection
            self.write_counts[src_ip].append(now)
            recent_writes = [t for t in self.write_counts[src_ip] if now - t < 60]
            self.write_counts[src_ip] = recent_writes
            if len(recent_writes) > 20:
                self.alerts.append(ModbusAlert(
                    severity="HIGH",
                    alert_type="WRITE_FLOOD",
                    src_ip=src_ip, dst_ip=dst_ip,
                    unit_id=modbus["unit_id"],
                    func_code=modbus["func_code"],
                    description=f"Excessive write rate: {len(recent_writes)} writes in 60s from {src_ip}",
                    mitre_technique="T0836 - Modify Parameter",
                ))

        # Detection Rule 3: Anomalous function code
        if session_key in self.allowed_function_codes:
            if modbus["func_code"] not in self.allowed_function_codes[session_key]:
                self.alerts.append(ModbusAlert(
                    severity="HIGH",
                    alert_type="ANOMALOUS_FUNCTION_CODE",
                    src_ip=src_ip, dst_ip=dst_ip,
                    unit_id=modbus["unit_id"],
                    func_code=modbus["func_code"],
                    description=(
                        f"Function code {modbus['func_code']} ({MODBUS_FUNC_NAMES.get(modbus['func_code'], 'Unknown')}) "
                        f"not in baseline for {session_key}"
                    ),
                    mitre_technique="T0855 - Unauthorized Command Message",
                ))

        # Detection Rule 4: Broadcast write (unit ID 0)
        if modbus["unit_id"] == 0 and modbus["func_code"] in MODBUS_WRITE_FUNCTIONS:
            self.alerts.append(ModbusAlert(
                severity="CRITICAL",
                alert_type="BROADCAST_WRITE",
                src_ip=src_ip, dst_ip=dst_ip,
                unit_id=0,
                func_code=modbus["func_code"],
                description="Broadcast write command (unit ID 0) affects ALL Modbus devices on segment",
                mitre_technique="T0855 - Unauthorized Command Message",
            ))

        # Detection Rule 5: Out-of-range register access
        if "start_address" in modbus and session_key in self.allowed_register_ranges:
            addr = modbus["start_address"]
            qty = modbus.get("quantity", 1)
            in_range = any(
                start <= addr and addr + qty <= end
                for start, end in self.allowed_register_ranges[session_key]
            )
            if not in_range:
                self.alerts.append(ModbusAlert(
                    severity="HIGH",
                    alert_type="OUT_OF_RANGE_REGISTER",
                    src_ip=src_ip, dst_ip=dst_ip,
                    unit_id=modbus["unit_id"],
                    func_code=modbus["func_code"],
                    description=f"Register access {addr}-{addr+qty} outside baseline ranges",
                    mitre_technique="T0836 - Modify Parameter",
                ))

        # Detection Rule 6: Diagnostic/restart commands
        if modbus["func_code"] in MODBUS_DIAGNOSTIC_FUNCTIONS:
            self.alerts.append(ModbusAlert(
                severity="HIGH",
                alert_type="DIAGNOSTIC_COMMAND",
                src_ip=src_ip, dst_ip=dst_ip,
                unit_id=modbus["unit_id"],
                func_code=modbus["func_code"],
                description=f"Diagnostic function code {modbus['func_code']} detected - potential DoS or reconnaissance",
                mitre_technique="T0814 - Denial of Service",
            ))

    def print_report(self):
        """Print detection report."""
        print(f"\n{'='*70}")
        print(f"MODBUS COMMAND INJECTION DETECTION REPORT")
        print(f"{'='*70}")
        print(f"Analysis Time: {datetime.now().isoformat()}")
        print(f"Total Packets Analyzed: {self.packet_count}")
        print(f"Modbus Packets: {self.modbus_count}")
        print(f"Alerts Generated: {len(self.alerts)}")

        if self.alerts:
            severity_counts = defaultdict(int)
            for alert in self.alerts:
                severity_counts[alert.severity] += 1

            print(f"\nSeverity Distribution:")
            for sev in ["CRITICAL", "HIGH", "MEDIUM", "LOW"]:
                if sev in severity_counts:
                    print(f"  {sev}: {severity_counts[sev]}")

            print(f"\nDetailed Alerts:")
            for alert in self.alerts:
                print(f"\n  [{alert.severity}] {alert.alert_type}")
                print(f"    Time: {alert.timestamp}")
                print(f"    Source: {alert.src_ip} -> {alert.dst_ip}")
                print(f"    Unit ID: {alert.unit_id}")
                print(f"    Function: {alert.func_name} (FC {alert.func_code})")
                print(f"    Detail: {alert.description}")
                if alert.mitre_technique:
                    print(f"    MITRE ATT&CK ICS: {alert.mitre_technique}")

    def start_live_monitoring(self, interface: str, duration: int = 0):
        """Start live Modbus traffic monitoring."""
        print(f"[*] Starting Modbus monitoring on {interface}...")
        print(f"[*] Press Ctrl+C to stop")
        try:
            sniff(
                iface=interface,
                filter="tcp port 502",
                prn=self.analyze_packet,
                timeout=duration if duration > 0 else None,
            )
        except KeyboardInterrupt:
            pass
        self.print_report()


if __name__ == "__main__":
    detector = ModbusInjectionDetector(
        baseline_file=sys.argv[2] if len(sys.argv) > 2 else None
    )

    if len(sys.argv) >= 2:
        if sys.argv[1].endswith(".pcap") or sys.argv[1].endswith(".pcapng"):
            from scapy.all import rdpcap
            print(f"[*] Analyzing capture file: {sys.argv[1]}")
            packets = rdpcap(sys.argv[1])
            for pkt in packets:
                detector.analyze_packet(pkt)
            detector.print_report()
        else:
            detector.start_live_monitoring(sys.argv[1])
    else:
        print("Usage:")
        print("  Live:    python modbus_detector.py <interface> [baseline.json]")
        print("  Offline: python modbus_detector.py <capture.pcap> [baseline.json]")

Step 2: Deploy Suricata Rules for Modbus Attack Detection

# Suricata IDS Rules for Modbus Command Injection Detection
# Reference: MITRE ATT&CK for ICS, FrostyGoop analysis

# Unauthorized Modbus write from non-engineering workstation
alert modbus !$MODBUS_AUTHORIZED_WRITERS any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Unauthorized write operation detected";
  modbus_func:write_single_coil;
  flow:to_server,established;
  classtype:attempted-admin;
  sid:4000001; rev:1; priority:1;
)

alert modbus !$MODBUS_AUTHORIZED_WRITERS any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Unauthorized write multiple registers";
  modbus_func:write_multiple_registers;
  flow:to_server,established;
  classtype:attempted-admin;
  sid:4000002; rev:1; priority:1;
)

# Modbus broadcast write affecting all slaves
alert modbus any any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Broadcast write command (Unit ID 0)";
  modbus_unit_id:0;
  flow:to_server,established;
  classtype:attempted-admin;
  sid:4000003; rev:1; priority:1;
)

# Excessive Modbus write rate (potential automated attack)
alert modbus any any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Excessive write rate - possible automated attack";
  modbus_func:write_multiple_registers;
  flow:to_server,established;
  threshold:type threshold, track by_src, count 20, seconds 60;
  classtype:attempted-admin;
  sid:4000004; rev:1;
)

# Modbus diagnostics/restart command
alert modbus any any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Diagnostics function code detected";
  modbus_func:diagnostics;
  flow:to_server,established;
  classtype:attempted-dos;
  sid:4000005; rev:1;
)

# FrostyGoop-pattern: write to specific register ranges used for heating control
alert modbus any any -> $OT_PLC_SUBNET 502 (
  msg:"MODBUS-INJECT Potential FrostyGoop - write to heating control registers";
  modbus_func:write_multiple_registers;
  content:"|00 10|"; offset:8; depth:2;
  flow:to_server,established;
  classtype:attempted-admin;
  sid:4000010; rev:1; priority:1;
)

Key Concepts

TermDefinition
Modbus TCPIndustrial protocol operating on TCP port 502, lacking authentication or encryption, making it vulnerable to command injection
Function CodeSingle byte in Modbus PDU specifying the operation (read coils, write registers, diagnostics); monitoring for unauthorized function codes is key to detection
MBAP HeaderModbus Application Protocol header in TCP variant containing transaction ID, protocol ID, length, and unit ID
FrostyGoopFirst known malware using Modbus TCP for real-world operational impact, disrupted Ukrainian district heating in 2024
Unit IDAddress of the target Modbus slave device; Unit ID 0 is a broadcast affecting all slaves
Register RangeSpecific memory addresses in the PLC; legitimate operations access known ranges; out-of-range access indicates reconnaissance or manipulation

Common Scenarios

Scenario: FrostyGoop-Style Heating Control Attack

Context: A building automation system uses Modbus TCP to control HVAC equipment. Monitoring detects unexpected write commands to heating control registers from an IP not associated with any authorized BMS controller.

Approach:

  1. Verify the source IP against the authorized Modbus master list
  2. Check if any authorized maintenance or configuration change is in progress
  3. Capture full Modbus transaction including register addresses and values being written
  4. Compare written values against safe operating ranges for the heating equipment
  5. If unauthorized, immediately block the source IP at the industrial firewall
  6. Inspect the source device for compromise indicators (malware, unauthorized remote access)
  7. Verify current setpoints on all affected controllers against known-good values
  8. Restore safe setpoints if manipulation is confirmed

Pitfalls: Modbus lacks authentication, so the source IP is the only identifier -- attackers can spoof IPs if ARP protections are not in place. Do not assume all writes are malicious; legitimate SCADA operations include writes. Always verify against the change management log before escalating.

Output Format

MODBUS INJECTION DETECTION REPORT
====================================
Analysis Period: [start] to [end]
Monitoring Point: [interface/SPAN description]

TRAFFIC SUMMARY:
  Total Modbus Packets: [count]
  Read Operations: [count]
  Write Operations: [count]
  Unauthorized Writes Detected: [count]

ALERTS:
  [CRITICAL] Unauthorized write from [IP] to PLC [IP]
    Function: Write Multiple Registers (FC 16)
    Registers: [start]-[end]
    MITRE: T0855 - Unauthorized Command Message

BASELINE DEVIATIONS:
  New Modbus masters: [list]
  Unusual function codes: [list]
  Out-of-range register access: [list]

RECOMMENDED ACTIONS:
  1. Verify source [IP] authorization status
  2. Block unauthorized sources at industrial firewall
  3. Validate PLC register values against known-good state

리뷰

아직 리뷰가 없습니다. 사용해 본 소감을 남겨 주세요.

댓글

로그인 없이 쓸 수 있습니다. 사용 후기, 질문, 작동하지 않은 환경 등을 편하게 남겨 주세요.

아직 댓글이 없습니다. 첫 댓글을 남겨 보세요.

보내면 바로 공개됩니다. 이메일 주소나 전화번호 같은 개인 정보는 쓰지 마세요. URL은 2개까지입니다.

0 / 1,000자

이 양식은 reCAPTCHA로 보호되며 Google 개인정보처리방침 및 서비스 약관이 적용됩니다.

같은 저장소의 스킬

Assess exposure of Windows secrets protected by DPAPI, the operating system’s data protection service, during authorized security tests. Guide examination and decryption of saved credentials and browser data using available user sessions, credentials, or backup keys.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Assessing saved credential exposure in authorized tests
  • Examining collected DPAPI files offline
  • Reviewing protected browser and RDP credentials
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

Assess Shadow Credentials account takeover during authorized Active Directory testing. Examine permissions that allow public key registration, validate authentication without a password reset, and document credential cleanup, detection opportunities, and access control changes needed for remediation.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Assessing risky permissions identified in BloodHound
  • Validating account takeover without resetting a password
  • Generating directory change records during security exercises
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

Prepare for CMMC Level 2, a cybersecurity certification for defense contractors. Define the systems handling controlled information, review security requirements, calculate the SPRS assessment score, and organize remediation plans and evidence into a readiness report.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Define the assessment scope for systems handling controlled information
  • Calculate an SPRS score and prioritize unmet security requirements
  • Prepare security plans, remediation milestones, and assessment evidence
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

Create disk images for investigations using dd or dcfldd on Linux. The workflow covers write protection, bit-for-bit copying, hash checks to verify integrity, and documentation of the acquisition process.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Preserving a suspect drive before investigation
  • Creating evidence copies of USB devices or memory cards
  • Verifying that a disk image matches its source
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

Review Active Directory permissions with ldap3, a Python library for directory queries. Identify excessive access granted to non-administrative accounts, explain potential privilege escalation paths, and produce a JSON report with affected objects and remediation recommendations.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Auditing excessive Active Directory permissions
  • Investigating privilege escalation paths from ordinary accounts
  • Reporting affected objects and permission remediation recommendations
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

Inspect suspicious Android APK files without running them. Analyze permissions, app components, suspicious code patterns, and network indicators, then produce a JSON risk report to support malware triage and detection rule development.

한국어 요약은 준비 중입니다. 영어 요약을 표시하고 있습니다.

  • Triage suspicious APK files without running them
  • Inspect dangerous permission combinations and suspicious API calls
  • Extract network indicators for malware detection rules
mukul975/Anthropic-Cybersecurity-Skills3.5만2026년 8월 31일 업데이트

mukul975의 스킬 모두 보기

이 스킬의 문제 신고